CHOSUN

상용탑차용 냉동사이클의 성능특성에 관한 실험적 연구

Metadata Downloads
Author(s)
명치욱
Issued Date
2011
Abstract
Recently, the eating out culture has been developed due to the living level and quality elevation. Home-delivery service is increasing by demand of the refrigerated food. Accordingly, the freezing conveyance becomes the essential things all over the world, and it is rapidly increasing by actual demanding in the present-day life every year. However, the research is insufficient for the performance of refrigerating system in commercial refrigerator truck. In this study, the performance of refrigerating system was measured by changing from the TXV(thermal expansion valve) to EEV(electronic expansion valve) in order to improve responsiveness of expansion device.
As a result, the optimal refrigerant charging amount was determined by 1700 g for both system with TXV and EEV. In addition, COP of EEV system is a 1.61% higher than that of TXV system when the EEV opening is 75% which is optimal EEV opening. Besides, the performance of EEV system is higher than system of TXV system for variable driving conditions. The performance variation of EEV system with the operation condition is larger than that of EEV system. Under this condition, the optimal EEV opening was investigated and the correlations of system COP and mass flow rate verses EEV opening was developed ,
The regulation of the CFC, HCFC refrigerant was initiated due to the global warming problem. Hence, the natural refrigerant, CO2, is in the spotlight as the ultimate solution. The simulation modeling was developed based on the commercial refrigeration truck using CO2 in order to determine the applicability and consider the system performance characteristic according to driving conditions. In addition, the frost growth was considered to investigate the effect of frost on the system performance.
The system capacity of non-frost condition was determined by compressor volume which have the cooling capacity of 2.3 kW like that of refrigeration experimental condition. Besides, the system performance analysis was performed with indoor air temperature, outdoor air temperature, front air velocity and compressor speed in order to compared the system performance of non-frost condition. The system performance analysis was carried out with frost thickness so as to the investigate the effect of frost growth on the evaporator. The cooling capacity was analyzed every 5% decrease according to operating conditions.
As a result, it confirmed that the simulation results shows the similar tendency of experiment test. The cooling capacity was decreased by 33% when the frost thickness was 2 mm. The performance of CO2 refrigerating system showed similar trends compared with experiment results. As the frost thickness increased, the cooling capacity and compressor work was decreased simultaneously due to the reduction of heat transfer in the evaporator. Therefore, the system COP was decreased with frost growth.
Alternative Title
Experimental Study on Performance Characteristics of Refrigerating Cycle in the Refrigerator Car
Alternative Author(s)
Myung, Chi-wook
Affiliation
조선대학교 기계공학과
Department
일반대학원 기계공학과
Advisor
조홍현
Awarded Date
2012-02
Table Of Contents
Contents
List of Figures viii
List of Tables xi
Nomenclature xii
ABSTRACT xv

제 1 장 서 론 1
제 1 절 연구배경 1
제 2 절 상용탑차 냉동시스템의 기술개발 현황 5
제 3 절 기존연구 동향 9
제 4 절 연구목적 11

제 2 장 실험장치 및 방법(R404A system) 13
제 1 절 실험장치 13
제 2 절 측정장비 17
1. 온도측정 17
2. 압력 측정 19
3. 인버터 20
4. 압축기 소비동력 측정 22
5. 냉매의 질량유량 측정 23
6. 온습도 Sampler 25
7. 냉동용량의 계산 27
8. 풍량측정장치 28
9. 자료 수집 및 처리 프로그램 33
제 3 절 실험조건 35

제 3 장 실험결과 및 고찰 37
1. 냉매충전량에 따른 성능 고찰 37
2. EEV 개도에 따른 성능 고찰 39
3. 실내온도 변화에 따른 성능 고찰 41
4. 실외온도 변화에 따른 성능 고찰 43
5. 응축기 입구 풍속 변화에 따른 성능 고찰 45
6. 압축기 회전수 변화에 따른 성능 고찰 47
7. 최적 EEV 개도에서의 성능 고찰 49

제 4 장 냉동탑차용 CO2사이클 모델링 51
제 1 절 압축기 모델링 54
제 2 절 열교환기 모델링 56
1. 냉매측 열전달 상관식 59
2. 공기측 열전달 상관식 62
3. 서리층 해석 65
제 3 절 팽창장치 모델링 67
제 4 절 해석 조건 68

제 5 장 사이클 성능해석 결과 및 고찰 69
제 1 절 Non-frost 조건에서의 사이클 성능 고찰 69
제 2 절 서리성장에 따른 시스템의 성능 고찰 73
1. 고내온도 변화에 따른 성능 고찰(frost condition) 75
2. 실외온도변화에 따른 성능 고찰(frost condition) 78
3. 가스쿨러 입구 풍속변화에 따른 성능 고찰(frost condition) 81
4. 압축기 회전수변화에 대한 성능 고찰(frost condition) 85

제 6 장 결 론 88

Reference 90
Degree
Master
Publisher
조선대학교 기계공학과
Citation
명치욱. (2011). 상용탑차용 냉동사이클의 성능특성에 관한 실험적 연구.
Type
Dissertation
URI
https://oak.chosun.ac.kr/handle/2020.oak/9363
http://chosun.dcollection.net/common/orgView/200000256765
Appears in Collections:
General Graduate School > 3. Theses(Master)
Authorize & License
  • AuthorizeOpen
  • Embargo2012-02-02
Files in This Item:

Items in Repository are protected by copyright, with all rights reserved, unless otherwise indicated.